Description

Main

range of product

Altivar 212

 

product or component type

Variable speed drive

 

device short name

ATV212

 

product destination

Asynchronous motors

 

product specific application

Pumps and fans in HVAC

 

assembly style

With heat sink

 

network number of phases

3 phases

 

motor power kW

11 kW

 

motor power hp

15 hp

 

[Us] rated supply voltage

200...240 V - 15...10 %

 

supply voltage limits

170...264 V

 

supply frequency

50...60 Hz - 5...5 %

 

network frequency

47.5...63 Hz

 

EMC filter

Without EMC filter

 

line current

34.4 A 240 V
42.1 A 200 V

 

 

apparent power

17.6 kVA 240 V

 

prospective line Isc

22 kA

 

continuous output current

46.2 A 230 V

 

maximum transient current

50.8 A 60 s

 

speed drive output frequency

0.5...200 Hz

 

nominal switching frequency

12 kHz

 

switching frequency

12...16 kHz with derating factor
6...16 kHz adjustable

 

speed range

1...10

 

speed accuracy

+/- 10 % of nominal slip 0.2 Tn to Tn

 

torque accuracy

+/- 15 %

 

transient overtorque

120 % of nominal motor torque +/- 10 % 60 s

 

asynchronous motor control profile

Voltage/frequency ratio, 2 points
Voltage/frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/frequency ratio - Energy Saving, quadratic U/f
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)

 

regulation loop

Adjustable PI regulator

 

motor slip compensation

Adjustable
Automatic whatever the load
Not available in voltage/frequency ratio motor control

 

local signalling

1 LED red DC bus energized

 

output voltage

<= power supply voltage

 

isolation

Electrical between power and control

 

type of cable

IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR
IEC cable without mounting kit 1 45 °C copper 70 °C PVC
UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC

 

electrical connection

Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES
Terminal 25 mm² AWG 3 L1/R, L2/S, L3/T

 

tightening torque

4.5 N.m 40 lb.in L1/R, L2/S, L3/T
0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES

 

supply

Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 A overload and short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection

 

analogue input number

2

 

analogue input type

Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable PTC probe VIB 0...6 probes 1500 Ohm
Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits

 

sampling duration

2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog

 

response time

2 ms +/- 0.5 ms FM analog
7 ms +/- 0.5 ms FLA, FLC discrete
7 ms +/- 0.5 ms FLB, FLC discrete
7 ms +/- 0.5 ms RY, RC discrete

 

accuracy

+/- 0.6 % VIA for a temperature variation 60 °C
+/- 0.6 % VIB for a temperature variation 60 °C
+/- 1 % FM for a temperature variation 60 °C

 

linearity error

+/- 0.15 % of maximum value input VIA
+/- 0.15 % of maximum value input VIB
+/- 0.2 % output FM

 

analogue output number

1

 

analogue output type

Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits

 

discrete output number

2

 

discrete output type

Configurable relay logic FLA, FLC NO 100000 cycles
Configurable relay logic FLB, FLC NC 100000 cycles
Configurable relay logic RY, RC NO 100000 cycles

 

minimum switching current

3 mA 24 V DC configurable relay logic

 

maximum switching current

5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R
2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R
2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R

 

discrete input type

Programmable F 24 V DC level 1 PLC 4700 Ohm
Programmable R 24 V DC level 1 PLC 4700 Ohm
Programmable RES 24 V DC level 1 PLC 4700 Ohm

 

discrete input logic

Positive logic (source) F, R, RES <= 5 V >= 11 V
Negative logic (sink) F, R, RES >= 16 V <= 10 V

 

acceleration and deceleration ramps

Automatic based on the load
Linear adjustable separately from 0.01 to 3200 s

 

braking to standstill

By DC injection

 

protection type

Motor phase break motor
Break on the control circuit drive
Thermal power stage drive
Overvoltages on the DC bus drive
Against exceeding limit speed drive
Against input phase loss drive
With PTC probes motor
Input phase breaks drive
Line supply overvoltage and undervoltage drive
Line supply undervoltage drive
Overcurrent between output phases and earth drive
Overheating protection drive
Short-circuit between motor phases drive
Thermal protection motor

 

dielectric strength

2830 V DC between earth and power terminals
4230 V DC between control and power terminals

 

insulation resistance

>= 1 MOhm 500 V DC for 1 minute

 

frequency resolution

0.024/50 Hz analog input
0.1 Hz display unit

 

communication port protocol

APOGEE FLN
BACnet
LonWorks
METASYS N2
Modbus

 

connector type

1 RJ45
1 open style

 

physical interface

2-wire RS 485

 

transmission frame

RTU

 

transmission rate

9600 bps or 19200 bps

 

data format

8 bits, 1 stop, odd even or no configurable parity

 

type of polarization

No impedance

 

number of addresses

1...247

 

communication service

Monitoring inhibitable
Read device identification (43)
Read holding registers (03) 2 words maximum
Time out setting from 0.1 to 100 s
Write multiple registers (16) 2 words maximum
Write single register (06)

 

option card

Communication card LonWorks

 

operating position

Vertical +/- 10 degree

 

width

245 mm

 

height

330 mm

 

depth

190 mm

 

product weight

11.55 kg

 

power dissipation in W

459 W

 

air flow

157 m3/h

 

specific application

HVAC

 

IP degree of protection

IP21

 

discrete and process manufacturing

Building - HVAC : compressor for scroll
Building - HVAC : fan
Building - HVAC : pump

 

power range

7...11 kW at 200...240 V 3 phases

 

motor starter type

Variable speed drive

 

 

electromagnetic compatibility

Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test IEC 61000-4-11
1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
Electrostatic discharge immunity test level 3 IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3

 

pollution degree

2 IEC 61800-5-1

 

IP degree of protection

IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover EN/IEC 60529
IP21 EN/IEC 61800-5-1
IP21 EN/IEC 60529
IP41 on upper part EN/IEC 61800-5-1
IP41 on upper part EN/IEC 60529

 

vibration resistance

1 gn 13...200 Hz EN/IEC 60068-2-8
1.5 mm 3...13 Hz EN/IEC 60068-2-6

 

shock resistance

15 gn 11 ms IEC 60068-2-27

 

environmental characteristic

Classes 3C1 IEC 60721-3-3
Classes 3S2 IEC 60721-3-3

 

noise level

54 dB 86/188/EEC

 

operating altitude

1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without derating

 

relative humidity

5...95 % without condensation IEC 60068-2-3
5...95 % without dripping water IEC 60068-2-3

 

ambient air temperature for operation

-10...40 °C without derating
> 40...50 °C with derating factor

 

ambient air temperature for storage

-25...70 °C

 

standards

EN 61800-3
EN 61800-3 environments 1 category C1
EN 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C1
EN 61800-3 environments 2 category C2
EN 61800-3 environments 2 category C3
EN 61800-5-1
IEC 61800-3
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C2
IEC 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
IEC 61800-5-1
UL Type 1

 

product certifications

CSA
C-Tick
NOM 117
UL

 

marking

CE

 

 

Sustainable offer status

Green Premium product

 

RoHS (date code: YYWW)

Compliant  - since  1101  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity

 

REACh

Reference not containing SVHC above the threshold

 

Product environmental profile

Available Product environmental

 

Product end of life instructions

Available

 

Contractual warranty

Warranty period

18 months